Installation Requirements and Instructions
-
The following requirements for installation apply regardless of whether engineered openings or non-engineered openings are used to satisfy the NFIP requirements. You’ll find the technical information in the FAQs, but simply put, FEMA/NFIP requirements for flood vents include:
A minimum of one square inch of net open area for each square foot of enclosed area for non-engineered openings OR A minimum of ONE engineered inch for each square foot of enclosed area for an engineered opening.
A minimum of two vents per enclosed area, and each must be on at least two different sides of the exterior walls.
The bottom of the flood vent opening must not be higher than 12 inches above the adjacent grade.
The top of the opening must be below the Base Flood Elevation (BFE).
The opening in the wall must be at least 3” in diameter. This requirement refers to the hole in the wall and not the flood vent. See FEMA TECHNICAL BULLETIN – 2020 page 31.
View: FS Model: FS-1608 / FS-1616
View: FS Model: FS-1412 (For framed openings with studs 16” on center)
Frequently Asked Questions About Flood Vents.
-
Flood vents are permanent wall openings that allow floodwater to enter and exit an enclosed area automatically. They help equalize water pressure on foundation and enclosure walls, reducing the risk of structural damage during flooding.
-
A non-engineered opening is one that is simply measured by calculating the opening in the vent itself. It’s the amount of air/water flow or net open area that is used to meet FEMA requirements for Flood Vents. You will require 1 square inch of free area for each square foot of enclosed space to meet the FEMA requirements.
An engineered opening is one that is designed and certified by a registered engineer or architect as meeting certain performance characteristics describes in FEMA Technical Bulletin 1/08
If using an engineered vent then additional data must be provided. The “engineered openings must be certified by a design professional as having been designed to provide automatic equalization of hydrostatic flood forces by allowing for the entry and exit of flood waters.” In addition, the certification has to identify the building in which the engineered opening will be installed. Design requirements and specifications for certification statements are outlined in FEMA Technical Bulletin 1-08.